by absurddoctor 17 days ago
I was working at a data center in the financial district during Sandy. That was quite the experience. For whatever reason, our building was one of the last to have power turned back on. We never had to move diesel by hand fortunately. We did have a fun moment early on where one of our generators needed to have most of its load reduced for a few minutes. There were a pair of external fuel filters that needed to be changed fairly frequently. They were meant to be redundant so you could change one at a time. By the time we were able to get a tech on site, they were so dirty that when we started switching to just one the generator came very close to stalling out. After some conversation we thought it was thought that if we could drop the load enough we should be able to get away with just one dirty filter for a short period of time. The only chance we had at that was to shut down all of our cooling units. The generator was on the roof, and I was coordinating the timing over radio. You could dedinitely hear the generator wasn’t happy, but it worked. As soon as the second filter was replaced I let everyone know it was time to turn all of the cooling units back on. No one responded, and after a pause I realized that meant that probably no one had heard me and things were getting hot fast. I sprinted back inside. On the way my radio dropped, so once inside I sprinted to all of the units to tell people to turn them back on. For some reason I didn’t think about grabbing someone else’s radio. That may have been a lucky mistake though, as I’m not sure what all of those compressors turning at at the same time would have done.

I had made sure to observe the filter replacement process in case we needed to do it again ourselves. We did, and the next time someone recorded me doing it so everyone could learn and we handled most I’d the rest of the swaps from then on.

There were a lot of memorable experiences that week or so.

2 comments

We had the fuel filter issue at 75 Board street as well. After a few days we had to do a planned generator shutdown (the data center batteries could last a couple hours to give us coverage...) as a diesel mechanic flown in by Peer1 could service it. Props for handling that yourself!

Definitely a memorable week. I wonder just how many folks in Fidi were learning the finer points of emergency backup generators.

GS? That building is known to have one of the best backup power systems in the area, spent time there during the 2003 blackout.
I would have thought that backup generators would cumulatively run for maybe a few dozen days over their lifetime. How did the fuel filters get dirty so fast?
The _fuel_ itself goes bad. Diesel will slowly accumulate dissolved water, and once it gets past a certain threshold, a lot of wonderful bacteria start to flourish in it.

So you get clumps of gunk in your fuel that rapidly clogs the filters.

Because a genset that runs once a month and has a fuel tank sized for days of wide open operations is a textbook recipe for asphaltane and other garbage build up. Which of course you won't notice until you actually run the thing for a day straight and the fuel filters start showing it.
I was thinking the same thing: fix the sediment problem in your fuel tanks, fuel filters shouldn’t get dirty as fast as this story indicates.
Bargain-basement and/or very old fuel? Backup generators are not known for having their diesel cycled on the regular
Diesel fuel has to be periodically filtered ("polished") by passing it through cans of dessicant. It removes accumulated water and prevents bacterial growth. There are also biocide additives but they just _extend_ the periods between maintenance.

That's also why it's not a great idea to use diesel for your backup home generator. It will go bad sooner than you expect, and then you're left with drums of gunk that you can't dispose and can't use.

And gasoline won't help you either. It goes bad even faster.

Propane tanks are the best option they can sit in storage indefinitely.

Or pull an AT&T in Nashville and depend on natural gas for your backup generators.

Which doesn’t quite work so well when an explosion cuts your electrics and the fire department cuts the gas.

If you do still decide to depend on another energy grid for an energy grid failure, at least have roll-up generator hookups so you’re not spending a few days figuring out how to wire that up…

Best info I found was on Reddit: https://www.reddit.com/r/sysadmin/comments/kk3j0m/nashville_...

This is why tri-fuel generators are a thing too, very cool tech for not a lot of money.